Home   Browse database   Free examples   Contact us   Login
   
Navigation
Related links
20076 Chemical accident in France with oxygen (gas)
Go back to the accident listing

You do not have a membership or you are not logged in
Become a member
General accident information
Class/Quality * * *
Year 2003
Summary Clogged electrolysis liqour feed caused rise of
Temperature, short circuit, ignition of hydrogen/Temperature, short circuit, ignition of hydrogen
Oxygen mixture in electrolysis cell and explosion
In sodium chlorate workshop
Country F
Activity PROCESSING
Location CHEMICAL FACTORY
Chemicals Hydrogen (gas), Oxygen (gas), Oxygen (gas)
Cause Technical-failure
Fatalities/Injuries 0 / 0
Occurrences or events Block-of-system, Break, Clog, Explosion,
Ignition, Not-working, Overheating, Short-circuiting,
Wrong-composition, Wrong-composition
 
 
Full accident information 
download accident report Click here to view a document containing the full accident information

Country: FRANCE (F)
Date : 2003 1020


In a sodium chlorate workshop of a chemical factory, a short circuit ignited a hydrogen/ oxygen mixture in an electrolyses cell and caused a deflagration. The lid of the cell was made of a very thin polymer membrane (diaphragm) which broke as intended. An operator stopped the production. After analyses, it seemsed that the incident was due to clogging of the electrolysis liquor feed. This caused a rise in temperature of the contents of the cell and in the production of oxygen. The temperature surveillance system connected to an alarm did not work.

Lessons learned
1.
A regular surveillance of the system with recordings was implemented.
2.
A complete survey of the surveillance system was performed.



Dans l'atelier 'chlorate de sodium' d'une usine chimique, un court-circuit enflamme un m??lange oxyg??ne/hydrog??ne dans une cellule d'??lectrolyse et provoque une d??flagration. Le couvercle de la cellule est constitu??e par une tr??s mince membrane en polym??re plastique qui se rompt comme pr??vu. Un op??rateur arr??te la production. Apr??s analyse, l'accident serait d?? ?? un colmatage de l'alimentation en liqueur d'??lectrolyse ; ce dernier aurait provoqu?? la mont??e en temp??rature du contenu de la cellule et une augmentation de la production d'oxyg??ne. D'autre part, le syst??me de surveillance de la temp??rature reli?? ?? une alarme n'a pas fonctionn??. L'exploitant met en place sans d??lai une surveillance r??guli??re du syst??me avec des enregistrements par des ??quipes post??es. Ce dispositif sera compl??t?? par une alarme de surveillance sur le syst??me de multiplexage des mesures. Enfin, une ??tude compl??te du syst??me de surveillance est effectu??e pour fiabiliser l'installation.



 